BiRa Systems |
MODEL 8884
Rack Protection System
(RPS)
| FEATURES: Standalone or Ethernet, RS-232 & RS-485 Monitoring System Monitors 12 DC voltages in rack Monitors multiple AC voltages Monitors Inlet and Outlet Air Flow Monitors Temperature and Humidity Monitors H2O Temperature, Flow and Leak Detection Monitors Smoke Detector Capable of shutting off / Resetting AC power to multiple crates using 1 of many BiRa AC Relay Box Models Simple hard logic for reliability Remote parallel port status readout and loud audible alarm Low cost, compact 1U chassis, 19" rack mount |
|
| . |
|
APPLICATIONS: RPS / ETHERNET The RPS main chassis includes an Ethernet Data Acquisition System. This provides 32 I/O channels, programmable in four byte-wide (8-bit) ports. Port3 default configuration is set to power-up in output mode with zero level outputs, this initializes the RPS control. Ports other than port3 always power-up as input ports. Ports 0,1 and 2 must be set to input operation with port3 set to output operation after power-up. The port settings are of critical importance. Features and Benefits include, Direct 10Base-T Ethernet interface with TCP/IP protocol and two serial ports for monitoring/controlling RS-232 and RS-485 devices. This functionality provides a relatively effortless way to add industrial serial device network elements to Ethernet. MODEL 8884 RPS ( Rack Protection System ) DIGITAL I/O SYSTEM KEY FEATURES/BENEFITS
DESCRIPTION Digital I/O Each 8884-1001E provides 32 digital I/O channels, programmable in four byte-wide (8-bit) sections, or ports. Each digital port is TTL-level compatible and can be independently programmed for input or output. Trough local signal processing, various digital input/output functions are supported. Inputs can be used to read the current status of digital signals, detect signal state-changes (latch a state), and count events up to 250Hz. Outputs can operate in simple on/off fashion, or can be programmed for specific delay times and on/off times for control and timing applications. In addition, eight of the digital output channels can be individually configured for predetermined output states at power up. All inputs and outputs are protected from damage under power on and power off conditions. High-Speed Counters Two 16-bit high-speed programmable counters capable of counting TTL level signals up to 250kHz are also provided. These counters also perform direct frequency measurement. High-speed counter inputs are made available by multiplexing them with digital input lines. Serial I/O RPS systems also feature serial I/O capabilities. An on-board RS-232 port can be used for both configuration and I/O applications. When the RS-232 port is in "Configuration Mode", any terminal device or computer with an RS-232 port can be used to program the unit's IP address, subnet mask and gateway parameters. With the port in "Command Mode", RPS units can monitor and control almost any device with RS-232 connectivity, including instruments, scales, gauges, smart sensors, machines and terminals. RPS systems which feature RS-485 I/O capabilities are also available. In addition to analog, digital and PS-232 I/O capabilities, these units monitor and control any number of instruments, sensors, and machines with RS-485 connectivity. Data Retention The 8884-1001E protects your data in the event of power outage. After power is lost, the unit will retain state and count values on each channel for up to five days. MODEL 8884 RPS ( Rack Protection System ) ANALOG AND DIGITAL I/O SYSTEM KEY FEATURES/BENEFITS 16SE/8DIFF Analog Inputs at- Net Link drivers for Windows 3.x/9.x/NT, UNIX and DOS available with complete documentation Windows NT COM Port Driver Third Party I/O drivers available for Intellution FIX, Wonderware InTouch, USDATA FactoryLink, and National Instruments LabVIEW DESCRIPTION Analog I/O The 8884-1031E Series and 8884-1002 Series can be configured for 16 single-ended or for 8 differential analog input channels through software. The 8884-1031E Series unit provides high-accuracy 16-bit resolution for the analog input channels and the 8884-1003E Series offers analog input channels with 12-bit resolution. Both units are also equipped with two analog output channels. They provide voltage outputs at 12-bit resolution with a ± 10 V output range. One rate generator is also provided for pacing analog input acquisitions. The timebase for the rate signal is derived from an internal 4 MHz crystal oscillator, allowing rates from 0.01 Hz to 100 kHz to be programmed. Digital I/O The 8884-1031E and 8884-1002E Series provide 16 TTL compatible digital I/O channels. Digital I/O channels are programmable in two bite-wide (8-bit) sections, or ports. Through local signal processing, Various digital input/output functions are supported. Digital input can be used to read the current status of digital signals, detect signal state-changes (latch a state), and count events up to 250 Hz. Outputs can operate in simple on/off fashion, or can be programmed for specific delay times and on/off times for control and timing applications. All inputs and outputs are protected from damage under power on and power off conditions. High-Speed Counters The 8884-1031E and 8884-1002E Series include one 16-bit high-speed counter channel. The input of this counter is made available by multiplexing it with one of the digital input lines. This counter can perform high-speed event counting on TTL level signals up to 250 kHz. Additionally, the counter can perform direct frequency measurements. Serial I/O RPS system also feature serial I/O capabilities. An on-board RS-232 port can be used for both configurations and I/O applications. When the RS-232 port is in "Configuration Mode", any terminal device or computer with an RS-232 port can be used to program the unit's IP address, subnet mask and gateway parameters. With the port in Command Mode", RPS units can monitor and control almost any device with RS-232 connectivity, including instruments, scales, gauges, smart sensors, machines and terminals. RPS systems which feature RS-485 I/O capabilities are also available. In addition to analog, digital and RS-232 capabilities, these units monitor and control any number of instruments, sensors, and machines with RS-485 connectivity.
|
| PORT0_bit0 = Main Alarm PORT0_bit1 = Main Warn PORT0_bit2 = Vmon-Alarm PORT0_bit3 = Vmon-Warn PORT0_bit4 = Ext.-Alarm PORT0_bit5 = Smoke-Alarm PORT0_bit6 = Vac-Alarm PORT0_bit7 = Spare-1 PORT2_bit0 = AirFlowOut-Warn PORT2_bit1 = AirFlowOut-Alarm PORT2_bit2 = AirTempDiff-Alarm PORT2_bit3 = H2Oleak-Alarm PORT2_bit4 = AirTemp-Warn PORT2_bit5 = Humidity-Warn PORT2_bit6 = AirFlowIn-Warn PORT3_bit7 = AirFlowIn-Alarm |
PORT1_bit0 = H2Oflow-Warn PORT1_bit1 = H2Oflow-Alarm PORT1_bit2 = H2OTemp-Warn PORT1_bit3 = H2OTemp-Alarm PORT1_bit4 = Spare-2 PORT1_bit5 = AirTempDiff-Warn PORT1_bit6 = Spare-3 PORT1_bit7 = AirTemp-Alarm PORT3_bit0 = Alarm Silence PORT3_bit1 = Clear Display PORT3_bit2 = Output Reset PORT3_bit3 = Smoke Det. Reset PORT3_bit4 = Vac Reset PORT3_bit5 = Spare-4 PORT3_bit6 = Spare-5 PORT3_bit7 = Spare-6 |
Place a Request For Quotation or Purchase Order with Bi Ra Systems
| Feedback | info@bira.com | Home Page |
Bi Ra Systems,
Incorporated
2404 Comanche Road NE
Albuquerque, New Mexico 87107
Ph : 505-881-8887
Fax:505-888-0651