BiRa Systems

Rack Protection System

MODEL 8884
Rack Protection System
(RPS)

FEATURES:
Standalone or Ethernet, RS-232 & RS-485 Monitoring System
• Monitors 12 DC voltages in rack
• Monitors multiple AC voltages 
• Monitors Inlet and Outlet Air Flow
• Monitors Temperature and Humidity
• Monitors H2O Temperature, Flow and Leak Detection
• Monitors Smoke Detector
• Capable of shutting off / Resetting AC power to multiple crates using
  1 of many BiRa AC Relay Box Models
• Simple hard logic for reliability
• Remote parallel port status readout and loud audible alarm
• Low cost, compact 1U chassis, 19" rack mount

.

APPLICATIONS:
• Ethernet interface with TCP/IP protocol
• Two serial ports for monitoring & controlling RS-232 and RS-485 devices
• Protection of expensive electronic systems for VME, CAMAC, VXI, CPCI, Fastbus ect.
• Racks using forced air-cooling or water cooling.

GENERAL Description:
The Bi Ra Model 8884 Rack Protection System is a detection system designed for the measurement, announcement and control of potentially damaging conditions inside an equipment rack. This simple, but effective system, protects your vital equipment from excessive heat, water/smoke damage, ect. The RPS provides a warning and or alarm status. Selectively enable or disable any individual warning or alarm in any combination.The RPS is capable of monitoring 3 crates, a total of 12DC voltages in a rack. The voltages can range from 2V to 24V DC with a resistor value in main chassis being changed for the various voltages being monitored. The system was designed to operate from +/- 12V DC since most sensors require these voltages.

RPS / ETHERNET
This unit is capable of remote monitor and control functions. The system responds with a "Main Alarm" or "Main Warning" associated with a individual response based upon enabled items. Control functions may be initiated at any time to disable responses or reset conditions. Upon receiving an alarm the RPS responds by disconnecting multiple Vac inputs unless this function is disabled, leaving control to the operator.

The RPS main chassis includes an Ethernet Data Acquisition System. This provides 32 I/O channels, programmable in four byte-wide (8-bit) ports. Port3 default configuration is set to power-up in output mode with zero level outputs, this initializes the RPS control. Ports other than port3 always power-up as input ports. Ports 0,1 and 2 must be set to input operation with port3 set to output operation after power-up. The port settings are of critical importance. Features and Benefits include, Direct 10Base-T Ethernet interface with TCP/IP protocol and two serial ports for monitoring/controlling RS-232 and RS-485 devices. This functionality provides a relatively effortless way to add industrial serial device network elements to Ethernet.

MODEL 8884 RPS ( Rack Protection System ) DIGITAL I/O SYSTEM

KEY FEATURES/BENEFITS

  • 32 Programmable Digital I/O Channels
  • Inputs programmable to read digital signal status, change-of-state and to perform event counting
  • Outputs can be programmed for normal (on/off), delayed, and variable delay/pulse-width models
  • Two 16-bit counter channels perform frequency measurement, high-speed event counting to 250kHz
  • Retain state and count information during loss of power
  • One RS-232 port monitors and controls instruments, gauges, smart sensors, machines and terminals
  • One RS-485 port monitors and controls instruments, smart sensors and machines
  • Synchronous and asynchronous client/server communications
  • Fully Supported by Visual DesignerÔ Application/MMI Generator Software for Windows
  • Net Link drivers for Windows 3.x/9.x/NT, UNIX and DOS available with complete documentation
  • Windows NT COM Port Driver
  • Third Party I/O drivers available for Intellution FIX, Wonderware InTouch, USDATA FactoryLink, and National Instruments LabVIEW

DESCRIPTION

Digital I/O

Each 8884-1001E provides 32 digital I/O channels, programmable in four byte-wide (8-bit) sections, or ports. Each digital port is TTL-level compatible and can be independently programmed for input or output. Trough local signal processing, various digital input/output functions are supported. Inputs can be used to read the current status of digital signals, detect signal state-changes (latch a state), and count events up to 250Hz. Outputs can operate in simple on/off fashion, or can be programmed for specific delay times and on/off times for control and timing applications. In addition, eight of the digital output channels can be individually configured for predetermined output states at power up. All inputs and outputs are protected from damage under power on and power off conditions.

High-Speed Counters

Two 16-bit high-speed programmable counters capable of counting TTL level signals up to 250kHz are also provided. These counters also perform direct frequency measurement. High-speed counter inputs are made available by multiplexing them with digital input lines.

Serial I/O

RPS systems also feature serial I/O capabilities. An on-board RS-232 port can be used for both configuration and I/O applications. When the RS-232 port is in "Configuration Mode", any terminal device or computer with an RS-232 port can be used to program the unit's IP address, subnet mask and gateway parameters. With the port in "Command Mode", RPS units can monitor and control almost any device with RS-232 connectivity, including instruments, scales, gauges, smart sensors, machines and terminals.

RPS systems which feature RS-485 I/O capabilities are also available. In addition to analog, digital and PS-232 I/O capabilities, these units monitor and control any number of instruments, sensors, and machines with RS-485 connectivity.

Data Retention

The 8884-1001E protects your data in the event of power outage. After power is lost, the unit will retain state and count values on each channel for up to five days.

MODEL 8884 RPS ( Rack Protection System ) ANALOG AND DIGITAL I/O SYSTEM

KEY FEATURES/BENEFITS

16SE/8DIFF Analog Inputs at-
16-bit Resolution - 8884-1031E
12-bit Resolution - 8884-1002E
Expandable up to 256 SE/128 Diff analog inputs using AI-MAX
Up to100kHz Sample Rate for 8884-1002E
Up to 45kHZ Sample Rate for 8884-1031E
Two 12-bit Analog Output Channels
16 Digit I/O Channels
Digital inputs can be programmed to read digital signal status, changer-of-state and to perform general-purpose event counting
Digital outputs can be programmed for normal (on/off), delayed, variable delay/pulse-width and square wave models
One programmable 16-bit counter performs frequency measurement, high-speed event counting up to 250kHz
One RS-232 port monitors and controls instruments, smart sensors, machines and terminals
One RS-485 port monitors and controls instruments, smart sensors and machines
Synchronous and asynchronous client/server communications
Fully Supported by Visual DesignerÔ
Application/MMI development software for Windows
Net Link drivers for Windows 3.x/9.x/NT, UNIX and DOS available with complete documentation
Windows NT COM Port Driver
Third Party I/O drivers available for Intellution FIX, Wonderware InTouch, USDATA FactoryLink, and National  Instruments LabVIEW

DESCRIPTION

Analog I/O

The 8884-1031E Series and 8884-1002 Series can be configured for 16 single-ended or for 8 differential analog input channels through software. The 8884-1031E Series unit provides high-accuracy 16-bit resolution for the analog input channels and the 8884-1003E Series offers analog input channels with 12-bit resolution.

Both units are also equipped with two analog output channels. They provide voltage outputs at 12-bit resolution with a ± 10 V output range.

One rate generator is also provided for pacing analog input acquisitions. The timebase for the rate signal is derived from an internal 4 MHz crystal oscillator, allowing rates from 0.01 Hz to 100 kHz to be programmed.

Digital I/O

The 8884-1031E and 8884-1002E Series provide 16 TTL compatible digital I/O channels. Digital I/O channels are programmable in two bite-wide (8-bit) sections, or ports. Through local signal processing, Various digital input/output functions are supported. Digital input can be used to read the current status of digital signals, detect signal state-changes (latch a state), and count events up to 250 Hz. Outputs can operate in simple on/off fashion, or can be programmed for specific delay times and on/off times for control and timing applications. All inputs and outputs are protected from damage under power on and power off conditions.

High-Speed Counters

The 8884-1031E and 8884-1002E Series include one 16-bit high-speed counter channel. The input of this counter is made available by multiplexing it with one of the digital input lines. This counter can perform high-speed event counting on TTL level signals up to 250 kHz. Additionally, the counter can perform direct frequency measurements.

Serial I/O

RPS system also feature serial I/O capabilities. An on-board RS-232 port can be used for both configurations and I/O applications. When the RS-232 port is in "Configuration Mode", any terminal device or computer with an RS-232 port can be used to program the unit's IP address, subnet mask and gateway parameters. With the port in Command Mode", RPS units can monitor and control almost any device with RS-232 connectivity, including instruments, scales, gauges, smart sensors, machines and terminals.

RPS systems which feature RS-485 I/O capabilities are also available. In addition to analog, digital and RS-232 capabilities, these units monitor and control any number of instruments, sensors, and machines with RS-485 connectivity.


Port and bit assignments are as follows :

PORT0_bit0 = Main Alarm
PORT0_bit1 = Main Warn
PORT0_bit2 = Vmon-Alarm
PORT0_bit3 = Vmon-Warn
PORT0_bit4 = Ext.-Alarm
PORT0_bit5 = Smoke-Alarm
PORT0_bit6 = Vac-Alarm
PORT0_bit7 = Spare-1

PORT2_bit0 = AirFlowOut-Warn
PORT2_bit1 = AirFlowOut-Alarm
PORT2_bit2 = AirTempDiff-Alarm
PORT2_bit3 = H2Oleak-Alarm
PORT2_bit4 = AirTemp-Warn
PORT2_bit5 = Humidity-Warn
PORT2_bit6 = AirFlowIn-Warn
PORT3_bit7 = AirFlowIn-Alarm
PORT1_bit0 = H2Oflow-Warn
PORT1_bit1 = H2Oflow-Alarm
PORT1_bit2 = H2OTemp-Warn
PORT1_bit3 = H2OTemp-Alarm
PORT1_bit4 = Spare-2
PORT1_bit5 = AirTempDiff-Warn
PORT1_bit6 = Spare-3
PORT1_bit7 = AirTemp-Alarm

PORT3_bit0 = Alarm Silence
PORT3_bit1 = Clear Display
PORT3_bit2 = Output Reset
PORT3_bit3 = Smoke Det. Reset
PORT3_bit4 = Vac Reset
PORT3_bit5 = Spare-4
PORT3_bit6 = Spare-5
PORT3_bit7 = Spare-6

Place a Request For Quotation or Purchase Order with Bi Ra Systems